Refrigeration units from Viessmann - Catalog - Page 18
PROGRAMME AND PERFORMANCE OVERVIEW
WSC2 - Packaged Food
Model
WSC2 900 PF
WSC2 1300 PF
WSC2 1800 PF
Cooling capacity [W] 1
900
1300
1800
Room volume up to [m³] ²
15
20
30
Cold room temperature adjustment range [°C]
+5 to +20
+5 to +20
+5 to +20
Allowed ambient
temperature [°C] ³
- 15 to +43
- 15 to +43
- 15 to +43
Refrigerant / GWP ⁴
R513A / 573
R513A / 573
R513A / 573
32/32
33/33
34 / 34
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
Circulating air
Circulating air
Circulating air
Dimensions condensing unit
HxWxD [mm]
837 x 942 x 654
837 x 942 x
654
600 x 900 x
350
Dimensions evaporator
HxWxD [mm]
176 x 928 x 515
176 x 928 x 515
455 x 752 x 430
Sound pressure [dB(A)] 5
Voltage / Phases /
Frequency [V/-/Hz]
Defrosting type
WSC2 - Packaged Food
Model
WSC2 2200 PF
WSC2 2800 PF
WSC2 4100 PF
WSC2 5500 PF
2200
2800
4100
5500
40
55
90
130
Cold room temperature adjustment range [°C]
+5 to +20
+5 to +20
+5 to +20
+5 to +20
Allowed ambient
temperature [°C] ³
- 15 to +43
- 15 to +43
- 15 to +43
- 15 to +43
Refrigerant / GWP ⁴
R513A / 573
R513A / 573
R513A / 573
R513A / 573
34 / 34
39 / 36
40 / 37
40 / 37
230 / 1 / 50
400 / 3 / 50
400 / 3 / 50
400 / 3 / 50
Circulating air
Circulating air
Circulating air
Circulating air
600 x 900 x
350
840 x 1030 x 425
840 x 1030 x 425
840 x 1030 x 425
455 x 752 x 430
455 x 752 x 430
455 x 1212 x 430
455 x 1212 x 430
Cooling capacity [W] 1
Room volume up to [m³] ²
Sound pressure [dB(A)] 5
Voltage / Phases /
Frequency [V/-/Hz]
Defrosting type
Dimensions condensing unit
HxWxD [mm]
Dimensions evaporator
HxWxD [mm]
1
Condensing unit; Evaporation temperature t₀ -5°C, ambient temperature + 32°C; evaporator superheat 10K; influences of installation location and other refrigeration
circuit components must be considered independently
2
Basis of calculation for room size: Room temperature +8°C, Ambient temperature +25°C, heat extraction from goods 15 K, operating time 16 h/day,
goods handling 1/7 per day, inspection and lighting 0.5 h / day
3
max. Compressor inlet superheat 20K
4
based on AR6 / IPCC
5
Condensing unit, A-weighted equivalent sound pressure level at 10m distance