Refrigeration units from Viessmann - Catalog - Page 13
PROGRAMME AND PERFORMANCE OVERVIEW
WSC2 - Fruits & Vegetables
Model
WSC2 2100 FV
WSC2 2700 FV
WSC2 3400 FV
WSC2 5000 FV
WSC2 6700 FV
2100 / 1800
2700 / 2300
3400 / 2800
5000 / 4200
6700 / 5700
35
50
65
105
150
+5 to +20
+5 to +20
+5 to +20
+5 to +20
+5 to +20
- 15 to +43
- 15 to +43
- 15 to +43
- 15 to +43
- 15 to +43
R513A / 573
R513A / 573
R513A / 573
R513A / 573
R513A / 573
34 / 34
34 / 34
39 / 36
40 / 37
40 / 37
230 / 1 / 50
230 / 1 / 50
400 / 3 / 50
400 / 3 / 50
400 / 3 / 50
Circulating air
Circulating air
Circulating air
Circulating air
Circulating air
Dimensions condensing unit
HxWxD [mm]
600 x 900 x 350
600 x 900 x 350
840 x 1030 x 425
840 x 1030 x 425
840 x 1030 x 425
Dimensions evaporator
HxWxD [mm]
455 x 752 x 430
455 x 752 x 430
455 x 1212 x 430
455 x 1212 x 430
455 x 1672 x 430
Cooling capacity [W] 1
Room volume up to [m³] 2
Cold room temperature
adjustment range [°C]
Allowed ambient
temperature [°C] ³
Refrigerant / GWP ⁴
Sound pressure [dB(A)] 5
Voltage / Phases /
Frequency [V/-/Hz]
Defrosting type
WSF2
Model
WSF2 1800
WSF2 2600
WSF2 3900
WSF2 4500
Cooling capacity [W] ⁶
1800 / 1500
2600 / 2200
3900 / 3300
4500 / 3800
15
30
50
60
-25 to -5
-25 to -5
-25 to -5
-25 to -5
- 15 to +43
- 15 to +43
- 15 to +43
- 15 to +43
R452A / 1945
R452A / 1945
R452A / 1945
R452A / 1945
39 / 36
40 / 37
40 / 37
41 / 38
400 / 3 / 50
400 / 3 / 50
400 / 3 / 50
400 / 3 / 50
Electrical
Electrical
Electrical
Electrical
840 x 1030 x 425
840 x 1030 x 425
840 x 1030 x 425
1245 x 1030 x 425
455 x 752 x 430
455 x 752 x 430
455 x 1212 x 430
455 x 1212 x 430
Room volume up to [m³] ⁷
Cold room temperature
adjustment range [°C]
Allowed ambient
temperature [°C] ³
Refrigerant / GWP ⁴
Sound pressure [dB(A)] 5
Voltage / Phases /
Frequency [V/-/Hz]
Defrosting type
Dimensions condensing unit
HxWxD [mm]
Dimensions evaporator
HxWxD [mm]
1
Condensing unit; Evaporation temperature t₀ 0°C, ambient temperature + 32°C / 43°C; Evaporator Superheat 10K; influences of installation location and other refrigeration
circuit components must be considered independently
2
Basis of calculation for room size: Room temperature +8°C, Ambient temperature +25°C, heat extraction from goods 15 K, operating time 16 h/day, goods handling 1/7 per
day, inspection and lighting 0.5 h / day
3
max. Compressor inlet superheat 20K
4
based on AR6 / IPCC
5
Condensing unit, A-weighted equivalent sound pressure level at 10m distance
6
Condensing unit; Evaporation temperature t₀ -30°C, ambient temperature + 32°C / 43°C; Evaporator Superheat 10K; influences of installation location and other refrigeration
circuit components must be considered independently
7
Basis of calculation for room size: Room temperature -21°C, Ambient temperature +25°C, heat extraction from goods 15 K, operating time 16 h/day, goods handling 1/7 per
day, inspection and lighting 0.5 h / day